Alarm description |
Possible causes |
Possible Solutions/ Corrective actions
|
Thermocouple broken wire fault |
- Loose thermocouple wire
- Damaged thermocouple
- Damaged thermocouple wire
|
- Check the thermocouple wires & connections.
- Use the second thermocouple element
- Use a new thermocouple
|
Thermocouple alarm (high temp) |
- High temperature from the process
- Inaccurate reading from the thermocouple
- Loose thermocouple wire
- Damaged thermocouple
- Damaged thermocouple wire
|
- Check the process for any possible changes
- Check the accuracy of the thermocouple
- Check the thermocouple wires & connections.
- Use the second thermocouple element
- Use a new thermocouple
|
High Temperature Limit Controller Fault (manual reset) |
- RTO chamber temperature is more than 1800F
|
- Check the process for any possible changes
- Check the thermocouple
- Check the air flows to the units
- Check the capacity of the unit. RTO may be overloaded.
- Check the status of the hot by pass ( if applicable)
- Check the alarm set point on the temperature limit controller
- Make sure that the alarm has been rest manually on the controller.
|
Low temperature warning alarm |
- RTO chamber temperature is less than 1425F when RTO is online
|
- Check the process for any possible changes
- Check the RTO ready temperature set point on the HMI screen
- Check the RTO ready temperature timer set point on the HMI screen
- Check the RTO differential temperature set point on the HMI screen
- Check the RTO burner PID loop
|
High hopper A temperature fault
High hopper B temperature fault |
- Hopper temperature is more than 425F.
|
- Check the thermocouples
- Check air flows to the unit
- Check RTO high hopper temperature set point on the HMI screen
- Check the poppet cycle time on the HMI screen
- Check the sealing on the unit
- Check VFD frequency
|
High Stack temperature |
- Stack temperature is more than 450F.
|
- Check the thermocouples
- Check air flows to the unit
- Check RTO high stack temperature set point on the HMI screen
- Check the poppet cycle time on the HMI screen
- Check the sealing on the unit
- Check VFD frequency
|
Poppet extension proximity switch fault
Poppet retraction proximity switch fault |
- PLC cannot confirm the position of the poppet
|
- Check the field wiring for any possible loose wire
- Check the proximity/reed switches for any possible damages
- Check the poppet fault timer set point on the HMI
- Check the poppet actuators
- Check the poppet travel speed
|
Low compressed air fault |
- Low compressed air pressure from the compressor
- Set point on the compressed air pressure switch on the RTO
|
- Adjust compressed air pressure switch
- Check air filter
- Check air line for possible debris
- Check the wiring for any possible loose wire
- Check the air compressor
|
Hydraulic unit temperature fault |
- High temperature on the hydraulic unit
|
- Check for any possible leaking on the unit
- Check the wiring for any possible loose wire
|
Hydraulic fluid level fault |
- Low hydraulic fluid level
|
Hydraulic fluid pressure fault |
- Low or high hydraulic fluid pressure
|
Combustion blower air flow fault |
- Low combustion air pressure
|
- Check the combustion blower rotation.
- Check the combustion blower motor starter. If it is tripped, it should be reset manually.
- Check the combustion line for possible debris
- Check the combustion air pressure differential switch set point
- Check the wiring for any possible loose wire
- Check the combustion blower air flow fault timer set point on the HMI
|
Main supply fan air flow switch fault |
- Low air pressure to the unit
|
- Check the main blower rotation.
- Check the main blower motor starter, soft starter or VFD.
- Check the RTO inlet for any possible debris
- Check the main supply fan air pressure differential switch set point
- Check the wiring for any possible loose wire
- Check the main supply fan air flow fault timer set point on the HMI
|
VFD Fault (manual reset) |
- VFD fault signal from the VFD panel
|
- Check the alarm history from the VFD panel.
|
Clear path damper fault
3-Way Damper Fault
Fresh air damper fault
Process isolation damper fault
Diverters fault
Puff damper fault
Hot by pass fault
Secondary fresh air damper fault
|
- PLC cannot confirm the position of the damper
|
- Check the wiring for any possible loose wire
- Check the proximity, reed or auxiliary switches
- Check the dampers actuator
- Check the damper fault timer set point on the HMI
- Check the 4-20ma signal on the actuator ( if applicable)
|
Low Gas Pressure Switch Fault (manual reset) |
- Not enough natural gas pressure
|
- Check the supplied gas
- Check the set point on the low gas pressure switch
- Check the wiring for any possible loose wire
- Make sure that the switch has been reset manually
|
High gas pressure switch fault |
- Excessive natural gas pressure
|
- Check the supplied gas
- Check the set point on the low gas pressure switch
- Check the wiring for any possible loose wire
- Make sure that the switch has been reset manually (Canada only)
|
No Flame Detected or Veri-Flame Fault |
- Burner monitoring system cannot confirm that flame exists
|
- Clean the UV scanner
- Check the wiring for any possible loose wire
- Check the ignitor
- Check the air/gas damper
- Check the ignition transformer
- Monitor the DC voltage at the burner monitoring system
- Consider burner fine tuning or tuning
|
Gas POC switch Fault |
- PLC cannot confirm that gas safety shut off valve is closed
|
- Check the safety shut off valve
- Check the indicator
- Check the wiring for any possible loose wire
- Check the gas POC (proof of closure) fault timer on the HMI
|
Low fire switch fault |
PLC cannot confirm that burner is at low fire position |
- Check the low fire switch on the burner or auxiliary switch on the burner actuator
- Check the burner actuator
- Check the 4-20ma signal on the burner actuator
- Check the mechanical linkage
- Check the wiring for any possible loose wire
- Check the burner low fire switch fault timer on the HMI
|
Low PLC battery |
PLC battery voltage is low (Mitsubishi only) |
- Consider changing the PLC battery
|
Low ambient temperature |
Ambient temperature is below gas train temperature rating |
|